Set Up and Calibration Procedures
Communications Set Up Group

50

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

Revision 7

7/08

Communications Set Up Group

Table 16 lists the parameters and selections available for the SET COMM group.

Table 16 Communications Set Up Group Parameters

Actuator Lower

Display
Prompt

Selections or

Range of Setting

Parameter Definition/PDA HercuLink Prompt

COMM


DIS

MODB

HART

COMMUNICATONS PARAMETERS

— Disables or enables

parameter displays for Modbus communciations set up.

Disabled

Locks out access to communications displays

and parameters.

Modbus

— Allows access to the communication displays

and settings for the parameters listed below.

HART

– selects HART as the communications protocol

ADDRES

1 to 99

default = 1

DEVICE ADDRESS

— Selects device address when used in

a Modbus communications loop. Select an address that is
unique to other devices on the communications link.

BAUD

2400
4800
9600

19.2k

default = 19.2k

BAUD RATE

— Selects the speed of data transfer. All

equipment on the link must be set to match the host setting.

XmtDLY

NONE

10ms
20ms
30ms
40ms
50ms

default = 20ms

RESPONSE DELAY

— Selects the time delay (in

milliseconds) before a response to a query is transmitted.

DBLBYT


FP B

FPBB

FP L

FPLB

default = FP B

FLOATING POINT DATA FORMAT

— Selects the format for

transferring floating point data.

Byte Order

Floating Point Big Endian format

0 1 2 3

Floating Point Big Endian format

with byte-swapped—

1 0 3 2

Floating Point Little Endian format

3 2 1 0

Floating Point Little Endian format

with byte-swapped—

2 3 0 1