Set Up and Calibration Procedures

Set Up Procedure

Revision 7

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

37

7/08

Step

Operation

Press

Result

5

Change the Value
or Selection

or

These keys increase or decrease the value, or display the next
available selection for the selected function prompt.

See Table 7, Set Up Tips for instructions to increase or decrease
a value quickly.

Change the value or selection to meet your needs.

NOTE: If the display flashes, you are trying to make an
unacceptable entry, or the value on the display is at its range
limit. The display may also show “KEYERR” (Key error).

6

Enter Value or
Selection

FUNCTION

or

SET UP

This key selects another function prompt.

This key selects another set up group.

NOTE: Pressing either key will cause the previously selected
value or selection to be entered into memory.

7

Exit Set Up mode

DISPLAY

Exits set up mode and returns actuator to the same state it was
in immediately preceding entry into the set up mode. Any
changes you have made are stored in memory.

If you do not press any keys for 30 seconds, the display times
out and reverts to the mode and display shown prior to entering
the set up mode.