Maintenance Set Up Group

Revision 7

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

59

7/08

Maintenance Set Up Group

The Maintenance set up group consists of information about actuator operation accumulated through time.
This information (or maintenance statistics) can be used to evaluate actuator operation and determine
predicted or scheduled maintenance periods. Table 22 lists the parameters and selections available for the
SET MAINTENANCE group.

Please note that maintenance statistics are written to the EEPROM every 8 hours. Therefore the statistics
are saved in the event of a power interruption.

Table 22 Maintenance Set Up Group Parameters

Actuator Lower

Display
Prompt

Selections or

Range of Setting

Parameter Definition/PDA HercuLink

®

Prompt

PDA users: The prompts are organized differently on your PDA’s

HercuLink

®

software. Grayed prompts are under Configuration, Maintenance. Non-grayed

prompts are under Maintenance.

TEMP

nnnn F *

ACTUATOR TEMPERATURE

Read Only. Displays the

current internal temperature of the actuator.

TEMPHI

nnnn F *

HIGH TEMPERATURE LIMIT

— Displays the high

temperature limit of the internal actuator temperature since it
was last reset.

TEMPLO

nnnn F *

LOW TEMPERATURE LIMIT

— Displays the low

temperature limit of the internal actuator temperature since it
was last reset.

hh:mm:ss

ACST

ACCUMULATED STALL TIME

Displays the accumulated

stall time of the actuator motor since it was last reset.

STARTS

nnnn

ACCUMULATED MOTOR STARTS

— Displays the

accumulated motor starts since it was last reset. Multiply
displayed value times 10

5

to get actual value. Range is 0 to

999,900,000.

RLnCNT

n

= 1, 2, 3 or 4

nnnn

RELAY CYCLE COUNTS

Displays the accumulated cycle

counts of a relay since it was last reset. One relay cycle is
when a relay is energized and deenergized. Multiply
displayed value times 10

5

to get actual value. Range is 0 to

999,900,000.

REGNn

n

= 0 to 9

nnnn

ACCUMULATED MOTOR STARTS

— Displays the

accumulated motor starts in the 1

st

10% of motor span since

it was last reset. See

Regions of Motor Travel (page 62). Multiply displayed value
times 10

5

to get actual value. Range is 0 to 999,900,000.

TOTDEG

nnnn

TOTAL DEGREES OF MOTOR TRAVEL

Displays the

total number of degrees of motor travel since it was last
reset. Multiply displayed value times 10

5

to get actual value.

Range is 0 to 999,900,000.