Set Up and Calibration Procedures

Calibration

Revision 7

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

77

7/08

Potentiometer position sensor

Mounting bracket

Figure 29 Location of potentiometer position sensor

Table 31 Load Position Sensor Factory Calibration

Step

Action

1

Reapply AC power to the actuator.

2

Press SET UP key to access the MAINT set up group. Press the FUNCTION key until the
display reads LD CAL.

Press the

or

keys until the display reads POS.

3

Perform the Calibrate Motor procedure exactly as in Table 26 Motor calibration must be
performed for the factory configured full span range (0-100%).

ATTENTION

When calibrating the motor to a short stroke range, you must reset the end-of-travel limit
switches. See Setting End-of-Travel Limit Switches.

4

When motor calibration is complete, the calibration is now stored as the factory calibration of
the actuator motor.