Table 6 keypad description – Honeywell HERCULINE 2000 User Manual

Page 40

Advertising
background image

Set Up and Calibration Procedures
Local Display and Keypad

32

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

Revision 7

7/08

Table 6 Keypad Description

Key or

LED Indicator

Function

SET UP

Places the actuator in the set up group select mode. Sequentially displays the set
up groups and allows the FUNCTION key to display function parameters within the
set up group.
See Set Up and Calibration Procedures (page 31)Error! Reference source not
found.

for descriptions of the various options available in the set up groups.

FUNCTION

Used in conjunction with the SET UP key to select the individual functions of a
selected configuration set up group.
Used during field calibration procedure.

MAN/AUTO Alternately

selects:

MAN

- Actuator is in Manual mode.

AUTO

- Actuator is in Automatic mode.

NOTE: When in Manual mode the POS display is automatically selected so you
can use the up and down arrow keys to drive actuator motor manually.
NOTE: This button is disabled if MAENAB is set to DIS. See Table 19 (page 53).

DISPLAY

Pressing this key repeatedly cycles through the operating parameters that can be
shown on the lower display.

INP –

Input. Shows the value of the actuator input.

OP

Output. Shows the value of the actuator output

DE –

Deviation. Shows deviation between input value and actuator position.

POS –

Position. Shows current actuator position.

INCREMENT

Increases the configuration values shown on the display. Also shown as

.

In manual mode and POSition display selected, pressing this key will drive actuator
motor in direction of increasing signal input.

DECREMENT

Decreases the configuration values shown on the display. Also shown as

.

In manual mode and POSition display selected, pressing this key will drive actuator
motor in direction of decreasing signal input.

Indicates the movement of the actuator arm in the counterclockwise direction.
NOTE: Actuator rotation is the direction of the output shaft when facing the end of
the shaft and refers to the direction of rotation on increasing signal.

Indicates the movement of the actuator arm in the clockwise direction.
NOTE: Actuator rotation is the direction of the output shaft when facing the end of
the shaft and refers to the direction of rotation on increasing signal.

STALLED

Indicates that the actuator has detected a motor stall condition.

ALARM

Indicates a programmed alarm condition exists.

MANUAL

Indicates actuator is in manual mode

AUTO

Indicates actuator is in automatic mode.

Advertising