Section 6

Electrical System

Part No. 80-1214-3

6-51

4. Disconnect water level probe from control board. Install jumper from control board “water level” terminal to

ground.

5. Move the toggle switch from ICE to OFF to ICE position. Wait 45 seconds, then monitor the Water Level Probe

light.

WATER LEVEL PROBE CLOSED OR SHORTED

1. Disconnect the water level probe from the control board.

2. Move the toggle switch to the ICE position, wait 45 seconds and then monitor the Water Level Probe light.

Step 5 Jumper “water level” terminal to ground

Water Level light is:

Compressor

Cause

On

Energizes

Replace water level probe wiring.

(Verify defective component – ohm wire from

connector to connector.)

Off

Remains de-energized

Replace control board.

Step 2 Disconnect water level probe from control board “water level” terminal

Water Level light is:

Compressor

Cause

Off

Remains de-energized

Clean water level probe.

On

Energizes

Replace control board.

SV2035

WATER LEVEL

PROBE LIGHT

DISCONNECT

WATER LEVEL PROBE.

JUMPER FROM

CONTROL BOARD

“WATER LEVEL” TO

GROUND

SV2036

DISCONNECT

WATER LEVEL PROBE.

WATER LEVEL

PROBE LIGHT