Electrical System

Section 6

6-56

Part No. 80-1214-3

FAN CYCLE CONTROL

Function

Cycles the condenser fan motor on and off to maintain
proper operating discharge pressure.

The fan cycling control closes on an increase in
discharge pressure and opens on a decrease in
discharge pressure.

Check Procedure

1. Verify fan motor windings are not open or grounded

and fan spins freely.

2. Connect a manifold gauge set to the ice machine.

3. Hook a voltmeter in parallel across the fan cycle

control, leaving wires attached.

4. Refer to chart below:

Model

Cut-In (Close)

Cut-Out (Open)

QF0800

QC0700

250 psig +/- 5

200 psig+/- 5

Discharge

Pressure:

Reading Should Be:

Fan Should Be:

above cut-in

0 volts

running

below cut-in

line voltage

off

Revised 8/2003