Electrical System

Section 6

6-32

Part No. 80-1214-3

QF2300

Automatic Shut-Off

3A. ICE RUN OUT

Ice will build up in the bin until it
contacts the bin level probe. After ice
contacts the bin level probe for 30
continuous seconds the liquid line
solenoid valve, equalization valve
and compressor de-energize. To
allow excess ice to run out, the gear
motor and the water float valve
solenoid remain energized for an
additional 4 minutes, then de-
energize.

SV2110

RELAY

K1

RELAY

K2

RELAY

K3

RELAY K4

(25)

L1

L2

(54)

(53)

LIQUID LINE

SOLENOID

CENTRIFUGAL

SWITCH

(65)

INTERNAL

OVERLOAD

START

RUN

GEARMOTOR

WATER FLOAT

VALVE

DUMP VALVE

(56)

(55)

(22)

(51)

(52)

7 AMP

FUSE

GROUND

(58)

(57)

EQUALIZATION

SOLENOID

C2

C1

(91)

(22)

3A. ICE RUN OUT (45 Seconds)

Toggle Switch

ICE

Bin Level Probe

CLOSED ( Ice Contacting probe)

Control Board Relays

#1

Liquid Line Solenoid Valve

OFF

#2

Dump Valve

OFF

#3

Gear Motor

ON

#$

Water Float Valve Solenoid Coil

ON

Revised 8/2003