Manitowoc Ice FLAKE/CHIPLET QF0400 User Manual

Page 119

Advertising
background image

Section 6

Electrical System

Part No. 80-1214-3

6-57

COMPRESSOR ELECTRICAL DIAGNOSTICS

The compressor will not start or will trip repeatedly on overload.

Check Resistance (Ohm) Values

NOTE: Compressor windings can have very low ohm
values. Use a properly calibrated meter.

Perform the resistance test after the compressor cools.
The compressor dome should be cool enough to touch
(below 120°F/49°C) to assure that the overload is closed
and the resistance readings will be accurate.

SINGLE PHASE COMPRESSORS

1. Disconnect power from the condensing unit and

remove the wires from the compressor terminals.

2. The resistance values must be within published

guidelines for the compressor. The resistance
values between C and S and between C and R,
when added together, should equal the resistance
value between S and R.

3. If the overload is open, there will be a resistance

reading between S and R, and open readings
between C and S and between C and R. Allow the
compressor to cool, then check the readings again.

THREE PHASE COMPRESSORS

1. Disconnect power from the condensing unit and

remove the wires from the compressor terminals.

2. The resistance values must be within published

guidelines for the compressor. The resistance
values between L1 and L2, between L2 and L3, and
between L3 and L1 should all be equal.

3. If the overload is open, there will be open readings

between L1 and L2, between L2 and L3, and
between L3 and L1. Allow the compressor to cool,
then check the readings again.

Check Motor Windings to Ground

Check continuity between all three terminals and the
compressor shell or copper refrigeration line. Scrape
metal surface to get good contact. If continuity is
present, the compressor windings are grounded and the
compressor should be replaced.

Determine if the Compressor is Seized

Check the amp draw while the compressor is trying to
start.

COMPRESSOR DRAWING LOCKED ROTOR

The two likely causes of this are:

Defective starting component

Mechanically seized compressor

To determine which you have:

1. Install high and low side gauges.

2. Try to start the compressor.

3. Watch the pressures closely.

A. If the pressures do not move, the compressor is

seized. Replace the compressor.

B. If the pressures move, the compressor is turning

slowly and is not seized. Check the capacitors
and start relay.

COMPRESSOR DRAWING HIGH AMPS

The continuous amperage draw on start-up should not
be near the maximum fuse size indicated on the serial
tag.

The voltage when the compressor is trying to start must
be within ±10% of the nameplate voltage.

Diagnosing Capacitors

If the compressor attempts to start, or hums and trips
the overload protector, check the starting
components before replacing the compressor.

Visual evidence of capacitor failure can include a
bulged terminal end or a ruptured membrane. Do not
assume a capacitor is good if no visual evidence is
present.

A good test is to install known good substitute
capacitor.

Use a capacitor tester when checking a suspect
capacitor. Clip the bleed resistor off the capacitor
terminals before testing.

Revised 8/2003

Advertising
This manual is related to the following products: