Section 6

Electrical System

Part No. 80-1214-3

6-13

Automatic Shut-Off

3A. ICE RUN OUT

Ice will build up in the bin until it
contacts the bin level probe. After ice
contacts the bin level probe for 30
continuous seconds the compressor
de-energizes. To allow excess ice to
run out, the gear motor and the water
float valve solenoid remain energized
for an additional 45 seconds, then
de-energize.

SV3126

RELAY

K1

GROUND

L1

L2 (N)

(21)

(65)

CONTACTOR

COIL

(90)

HIGH

PRESSURE

CUT-OUT

(95)

RELAY

K2

RELAY

K3

RELAY K4

(25)

10 AMP

FUSE

(46)

GEARMOTOR

(22)

(43)

(56)

WATER FLOAT

VALVE COIL

(52)

(22)

(55)

(51)

DUMP VALVE COIL

FAN MOTOR

(AIR-COOLED ONLY)

(41)

CONTACTOR

CONTACTS

L1

T1

C4

POTENTIAL

RELAY

RUN

CAPACITOR

C4

POTENTIAL

RELAY

CONTACTOR

COIL

C4

POTENTIAL

RELAY

C4

POTENTIAL

RELAY

(21)

RUN CAPACITOR

FAN CYCLE

CONTROL

OVERLOAD

COMPRESSOR

(49)

RUN

CAPACITOR

START

CAPACITOR

(31)

(62)

C5

C2

C1

C

R

S

(61)

(45)

3A. Ice Run Out (45 Seconds)

Toggle Switch

ICE

Bin Level Probe

Closed (Ice Contacting Probe)

Control Board Relays

#1

Contactor Coil

Open / OFF

Compressor

OFF

Condenser Fan Motor

OFF

#2

Dump Valve

OFF

#3

Gear Motor

ON

#4

Water Float Valve Solenoid Coil

ON

Revised 8/2003