Ice Machine Operation

Section 3

3-18

Part Number 80-1214-3

Removal from Service/Winterization

GENERAL

Special precautions must be taken if the ice machine
head section is to be removed from service for an
extended period of time or exposed to ambient
temperatures of 32°F (0°C) or below.

Follow the applicable procedure below.

1. Disconnect the electrical power at the circuit breaker

or the electric service switch.

2. Turn off the water supply.

3. Disconnect and drain the incoming ice-making water

line at the rear of the ice machine.

4. Disconnect drain tubing (from the inlet to dump

valve) and drain water into container and discard.

5. Make sure water is not trapped in any of the water

lines, drain lines, distribution tubes, etc.

WATER COOLED CONDENSING UNIT

1. Perform steps 1-6 in previous column.

2. Disconnect the incoming water and drain lines from

the water-cooled condenser.

3. Insert a large screwdriver between the bottom spring

coils of the water regulating valve. Pry upward to
open the valve.

Pry Open the Water Regulating Valve

4. Hold the valve open and blow compressed air

through the condenser until no water remains.

! Caution

If water is allowed to remain in the ice machine in
freezing temperatures, severe damage to some
components could result. Damage of this nature is
not covered by the warranty.