Section 6

Electrical System

Part No. 80-1214-3

6-9

Automatic Shut-Off

An 8 minute lockout starts when the
compressor de-energizes. When the
ice drops away from the bin level
probe the ice machine will begin an
initial start-up cycle, provided the “8
minute lock-out” has expired.

8 Minute Lock-out

The bin level light will flash until the 8
minute lock-out expires.

After the 8 minute lock-out expires
the bin level light will de-energize.

The 8 minute lock-out time can be
overridden by moving the ON/OFF/
ICE toggle switch from ICE to OFF
then back to ICE.

SV3039

RELAY

K1

GROUND

L1

L2 (N)

(21)

(65)

CONTACTOR

COIL

(90)

HIGH

PRESSURE

CUT-OUT

(95)

RELAY

K2

RELAY

K3

RELAY K4

(25)

10 AMP

FUSE

(46)

GEARMOTOR

(47)

GEARMOTOR

RUN CAPACITOR

(48)

(43)

(56)

WATER FLOAT

VALVE COIL

(52)

(22)

(55)

(51)

DUMP VALVE

COIL

FAN MOTOR

(AIR-COOLED ONLY)

(10)

(11)

(14)

(41)

CONTACTOR

CONTACTS

L1

T1

RUN

START

(44)

Automatic Shut-Off (Until Ice No Longer Contacts Bin Level Probe)

Toggle Switch

ICE

Bin Level Probe

Closed (Ice Contacting Probe)

Control Board Relays

#1

Contactor Coil

Open / OFF

Compressor

OFF

Condenser Fan Motor

OFF

#2

Dump Valve

OFF

#3

Gear Motor

OFF

#4

Water Float Valve Solenoid Coil

OFF

Revised 8/2003