Refrigerant Recovery/Evacuation and Recharging

REFRIGERANT RECOVERY/EVACUATION

Normal Self-Contained Model Procedures

Do not purge refrigerant to the atmosphere. Capture
refrigerant using recovery equipment. Follow the
manufacturer’s recommendations.

CONNECTIONS

Quick disconnect fittings are recommended to prevent
accidental release of refrigerant.

1. Suction side of the compressor through the suction

service valve.

2. Discharge side of the compressor through the

discharge service valve.

SELF-CONTAINED RECOVERY/EVACUATION

1. Place the toggle switch in the OFF position and

disconnect all power.

2. Install manifold gauges, charging cylinder/scale, and

recovery unit or two-stage vacuum pump.

Recovery/Evacuation Connections

3. Perform recovery or evacuation:

A. Recovery: Operate the recovery unit as directed

by the manufacturer’s instructions.

B. Evacuation prior to recharging: Pull the system

down to 500 microns. Then, allow the pump to
run for an additional half hour. Turn off the pump
and perform a standing vacuum leak check.

NOTE: Check for leaks using a halide or electronic leak
detector after charging the ice machine.

4. Refer to Charging Procedures.

Remote Air-Cooled Models

Do not purge refrigerant to the atmosphere. Capture
refrigerant using recovery equipment. Follow the

manufacturer’s recommendations.

Important

Manitowoc Ice, Inc. assumes no responsibility for
the use of contaminated refrigerant. Damage
resulting from the use of contaminated refrigerant is
the sole responsibility of the servicing company.

Important

Replace the liquid line drier before evacuating and
recharging. Use only a Manitowoc (O.E.M.) liquid
line filter drier to prevent voiding the warranty.

SV3055

BACKSEAT

BACKSEAT

OPEN

OPEN

MANIFOLD SET

LOW SIDE

ACCESS

VALVE

HIGH SIDE

ACCESS

VALVE

SCALE

OPEN

VACUUM

PUMP/

RECOVERY

UNIT

Important

Manitowoc Ice Inc. assumes no responsibility for the
use of contaminated refrigerant. Damage resulting
from the use of contaminated refrigerant is the sole
responsibility of the servicing company.