Manitowoc Ice FLAKE/CHIPLET QF0400 User Manual

Page 23

Advertising
background image

Section 2

Installation Instructions

Part No. 80-1214-3

2-11

Refrigeration System Installation

(QF2200/RFC2085 AND QF2300/RFC2385 ONLY)

USAGE WITH NON-MANITOWOC
CONDENSING UNITS

Manitowoc Condensing Units are specifically designed
for usage with a Manitowoc Flake/Chiplet Ice Machine
Head Sections. Manitowoc Flake/Chiplet Ice Machines
will not operate with non-Manitowoc condensing units.

Factory Equipment Refrigeration Amounts

ICE MACHINE HEAD SECTION

Each ice machine head section ships from the factory
with a R-404A refrigerant charge appropriate for line
sets up to 50’ in length (12.5 lbs.). The serial tag on the
ice machine indicates the refrigerant charge. Additional
refrigerant must be added for line set lengths between
50’ and 100’ (1.5 lbs.).

REMOTE CONDENSING UNIT

Each condensing unit ships from the factory pressurized
with 50/50 nitrogen helium mixture that must be removed
during the installation process (approximately 20 psig).

REFRIGERATION LINE SETS/TRAPS KIT

Refrigeration Rated Tubing and Trap Kits are shipped
capped with atmospheric pressure.

QuietQube®

Ice Machine

Remote Single

Circuit

Condenser

Line Set*

QF2200

QF2300

RFC2085

RFC2385

RC-20

RC-30

RC-50

Line Set

Suction Line

Liquid Line

Insulation

Thickness

RC 20/30/50

3/4 inch

(19.1 mm)

1/2 inch

(12.7 mm)

1/2”(13mm)

Suction Line

1/4” (7mm)
Liquid Line

!

Warning

Installation of a Remote Condensing Unit may require
the use of special equipment for placement. Trained
and qualified personnel are required for proper
rigging and lifting.

! Caution

The 60-month compressor warranty (including the 24-
month labor replacement warranty) will not apply if
the Manitowoc Ice Machine and remote Manitowoc
Condensing Unit are not installed according to
specifications. This warranty also will not apply if the
refrigeration system is modified with a condenser,
heat reclaim device, or other parts or assemblies not
manufactured by Manitowoc Ice, Inc.

! Caution

Never add more than nameplate charge to the
refrigeration system for any application.

!

Warning

Potential Personal Injury Situation

The ice machine head section contains the refrigerant
charge. Installation and brazing of the line sets must be
performed by a properly trained and EPA certified
refrigeration technician aware of the dangers of dealing
with refrigerant
charged equipment.

Revised 8/2003

Advertising
This manual is related to the following products: