Manitowoc Ice FLAKE/CHIPLET QF0400 User Manual

Page 133

Advertising
background image

Section 7

Refrigeration System

Part No. 80-1214-3

7-11

Cycle Time/24 Hour Ice Production/Refrigerant Pressure Charts

These charts are used as guidelines to verify correct ice
machine operation. Accurate collection of data is
essential to obtain the correct diagnosis.

Refer to “Refrigeration System Diagnostics” for the
data that must be collected. This list includes: before
beginning service, ice production check, installation/
visual inspection, water system checklist, ice
formation pattern, safety limits, safeguards and
suction pressure analysis.

Ice production checks that are within 10% of the
chart are considered normal. This is due to variances
in water and air temperature. Actual temperatures
will seldom match the chart exactly.

Zero out manifold gauge set before obtaining
pressure readings to avoid misdiagnosis.

Discharge and suction pressure are highest at the
beginning of the cycle. Suction pressure will drop
throughout the cycle. Verify the pressures are within
the range indicated.

All pressure readings must be obtained at the ice
machine head section. Lineset length will affect
pressures at the condensing unit.

QF400 SELF-CONTAINED AIR COOLED

NOTE: These characteristics may vary depending on
operating conditions.

24 Hour Ice Production

Operating Pressures

Air Temp.

Entering

Condenser

°F/°C

Water Temperature °F/°C

50/10.0

70/21.1

90/32.2

70/ 21.1

395

360

335

80/26.7

375

320

300

90/32.2

335

300

270

100/37.8

295

250

240

110/43.3

255

230

225

Air Temp. Entering

Condenser °F/°C

Freeze Cycle

Discharge

Pressure PSIG

Suction

Pressure PSIG

50/10.0

160-180

27-29

70/21.1

210-235

32-35

80/26.7

250-295

34-39

90/32.2

285-315

37-41

100/37.8

320-360

40-46

110/43.3

370-405

44-49

Revised 8/2003