Battery Test Setup

If Battery Test Setup is selected from the main menu, the following menu is

displayed:

Battery Test Setup
1. Setup One-time Delayed Battery Test
2. Setup Monthly Battery Test
3. Setup Quarterly Battery Test
4. Cancel Pending Battery Test
5. Display Next Scheduled Battery Test
6. Return to Main Menu
Enter Selection:

This menu allows you to schedule, review schedule, or cancel pending battery

tests. The following menu is displayed when 1---3 is selected:

Enter Starting Month (1---12):
Enter Day of Week, Sunday = 1, (1---7):
Enter Week of Month (1---5):
Enter Hour of Test (0---23):
Enter Minute of Test (0---59):

NOTE: Follow each entry with <CR>.

<CR> with no entry will return to Battery Test Setup Menu.

Enter the information at the prompt with a carriage return to schedule the battery

test.
If entry 4 is selected from the Battery Test Setup menu, you will be prompted to

enter “Y” to cancel all pending tests. This selection will only cancel pending tests

and will not stop a test currently in progress.
If entry 5 is selected from the Battery Test Setup menu, and if a Battery Test is

scheduled, the following menu is displayed:

Next Battery Test Scheduled
WK DAY MON HR:MN
4 FRI MAR 15:34

NOTE: Enter <CR> to return to Battery Test Setup Menu.
If 5 is selected and there are no tests scheduled, the following will be displayed:

No Battery Test Scheduled
Enter <CR> to return to Battery Test Setup Menu

NOTE: The unit will only perform one battery test in any 24 hour period.