Using the emergency power off pushbutton, Resetting ups system after emergency power off – Powerware 5075 kVA User Manual

Page 78

Advertising
background image

70

Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation

164291261 Rev. F 111503

Using the EMERGENCY POWER OFF Pushbutton

Emergency Power Off is initiated by the covered, red

EMERGENCY POWER OFF

pushbutton on the Monitor Panel. This pushbutton is protected by a clear plastic

shield to prevent accidental activation. In an emergency, you can press this

pushbutton to instantaneously open the input breaker and interrupt UPS output.

The UPS is cut off from utility power, and your critical load is de-energized. All

power to the critical load is lost. The UPS (including Bypass) remains locked off

until you reset the

EMERGENCY POWER OFF pushbutton.

WARNING:

All power to the critical load is lost when you press this pushbutton. You should

use this feature only in an emergency or when you want to de-energize the critical

load.

To restart the UPS after pressing the

EMERGENCY POWER OFF pushbutton,

follow the procedure “Resetting UPS System after Emergency Power Off” of this

chapter before starting the UPS.
NOTE: The Remote EMERGENCY POWER OFF option functions the same way as

the EMERGENCY POWER OFF pushbutton on the Monitor Panel.

To Use the EMERGENCY POWER OFF Pushbutton

1.

Raise the clear plastic shield covering the red

EMERGENCY POWER OFF

pushbutton on the Monitor Panel.

2.

Press the

EMERGENCY POWER OFF pushbutton.

The breakers open (you can hear them opening). The breaker

CB1 trips, and the

Emergency Power Off

PUSH TO RESET pushbutton on the UPS Control Panel pops

out. The UPS system shuts down.

Resetting UPS System after Emergency Power Off

CAUTION:

Do not attempt to restart the system until the cause of the emergency has been

identified and cleared.

The Emergency Power Off

PUSH TO RESET pushbutton is a small white button on

the UPS Control Panel. The

PUSH TO RESET pushbutton pops out and the CB1

switch trips when the

EMERGENCY POWER OFF pushbutton on the Monitor

Panel is activated.

To reset the UPS system:

1.

Press the Emergency Power Off

PUSH TO RESET pushbutton until it clicks in

and remains recessed.

2.

Move the

CB1 switch from the TRIPPED (center) position to OFF. The switch

should be difficult to move from the

TRIPPED position.

3.

The UPS system is now reset. To restart the UPS system, follow the procedure

at the beginning of this chapter.

Advertising