Chapter 16 product specifications, Product specifications, System input – Powerware 5075 kVA User Manual

Page 129

Advertising
background image

121

Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio

n

164201261 Rev. F 111503

Product Specifications

The following sections detail the input, output and

environmental specifications for the UPS system.

System

Models

Notes

Powerware BPIII HE 50

50 kVA, 40kW

50 Hz/60 Hz models

Powerware BPIII HE 62.5

62.5 kVA, 50kW

50 Hz/60 Hz models

Powerware BPIII HE 75

75 kVA, 60kW

60 Hz models

System Input

Operating Input

Voltage

208 VAC for operation from 177 VAC to 229 VAC (60 Hz only)

400 VAC for operation from 340 VAC to 440 VAC (50 Hz only)

480 VAC for operation from 408 VAC to 528 VAC (60 Hz only)

600 VAC for operation from 510 VAC to 660 VAC (60 Hz only)

Operating Input

Frequency Range

3 Hz of nominal (60 Hz)

Operating Input

Current

Battery Charge:

125% of full load for overload + battery charge

Actual load + 25% of full load for battery charge

Reduced for Generator:

Adjustable, set to 102%

Input Current

Harmonic Content

10% maximum over zero to full load based on 10% THD at full

load (with input filter option installed)

Power Walk-In

Typically 15---20 second rectifier ramp-up to full utility load

Power Factor

Minimum 0.9

Line Surges

6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801---4