Configuring the serial ports – Powerware 5075 kVA User Manual

Page 97

Advertising
background image

89

Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio

n

164201261 Rev. F 111503

Configuring the Serial Ports

You must configure the port for communications using the LCD screen and

pushbuttons on the UPS Monitor Panel.

Select

Port 1 or Port 2 (optional) from the Setup menu to display one of the Setup

Port screens. The screens for Port 1 and Port 2 are identical, and allow you to

specify settings for the two serial communication ports. Figure 43 shows the Setup

Serial Port 1 screen.

Statistics Graphics

Setup

Setup

Port 1

Uninterruptible Power System

UPS System Normal
Alarm:

None

Notice: None

03 JAN 1994 14:23:45

Events

Meters

Setup Serial Port 1

Rate

9600

Data/Stop

8

1

Handshaking

XON / XOFF

Save

NO

Time

Mode

TERMINAL

Port 2

Battery

100%

Percent

Figure 43. Setup Serial Port 1 Screen

A small return arrow ( ) appears in the upper right corner of the Setup Port screen.
This arrow is a reminder that you can press the

pushbutton on the Monitor

Panel to toggle the pushbuttons between the menu box and the information area.

If the scroll bar is in the menu box, press the

pushbutton to toggle to the

information area. The first setting (Mode) is highlighted. Press the

or

pushbutton to move the highlight to the setting you want to change. To scroll

through the available options for that setting, press the

or

pushbutton.

To save the settings upon exit from this screen, be sure the Save field is set to YES.

Advertising