Bypass mode – Powerware 5075 kVA User Manual

Page 50

Advertising
background image

42

Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation

164291261 Rev. F 111503

Bypass Mode

The UPS automatically switches to Bypass mode if it detects an overload, load

fault, or internal failure. The bypass source supplies the commercial AC power to

the load through an internal switch and an internal transformer.

CAUTION:

The critical load is not protected while the UPS is in Bypass mode.

Figure 19 shows the path of electrical power through the UPS system when the UPS

is operating in Bypass mode.

Bypass

Rectifier

K4

Input

Input

K3

CB1

(closed)

BATTERY

Path of electrical power

RECTIFIER

INVERTER

Output

TRANSFORMER

BYPASS

DC/DC

CONVERTER

CB2

(closed)

(MBP)

(open)

Input

Isolation

Transformer

(BIB)

(closed)

(MIS)

(closed)

OUTPUT

Figure 19. Path of Current Through the UPS in Bypass Mode

You can transfer the UPS from Normal mode to Bypass mode manually. However,

the UPS switches automatically to Bypass mode whenever the inverter can no

longer supply the critical load. If the UPS transfers to Bypass mode from Normal

mode due to any reason other than operator intervention, the UPS automatically

attempts to transfer back to Normal mode (up to three times within a 10-minute

period).
Bypass mode is a normal operating mode, and not an alarm condition. However, if

the UPS is unable to return to Normal mode following an automatic transfer to

Bypass mode, an alarm condition will be recorded.

Advertising