Chapter 11 using features and options, Using features and options, Building alarm monitoring – Powerware 5075 kVA User Manual

Page 79: Optional)

Advertising
background image

71

Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio

n

164201261 Rev. F 111503

Using Features and Options

The many standard features of your UPS provide consistent,

economical, and dependable power protection. In addition, you

can add available options and accessories to enhance the performance of your

UPS system. This chapter provides detailed descriptions of some of the features

and options introduced earlier in this manual.

Building Alarm Monitoring

This standard feature lets you connect the UPS to your building alarms, such as

smoke detectors or overtemperature alarms. The terminals for external

connections are located inside the UPS on the customer interface panel

(see Figure 35).

TB1

BLDG ALARM 1

BLDG ALARM 4

BLDG ALARM 5

NOTE:

All building alarm inputs or remote

features require an isolated, normally

open contact or switch (rated at 24 Vdc

20 mA minimum) connected between

the alarm input terminal and common

terminal as shown. All control wiring,

relay, and switch contacts are customer

provided.

1

2
3
4
5
6

7
8

9

15

10

11

14

13

12

TB2

BLDG ALARM 2

BLDG ALARM 3

BLDG ALARM 6

1

2
3
4
5
6

7
8

9

15

10

11

14

13

12

RS232

RS485

ON BYPASS

BATTERY CONTACTOR CLOSED

RELAY 2 NO

ON INV

RELAY 2 NC

RELAY 1 NO

RELAY 1 NC

BLDG ALARM 1 RTN

BLDG ALARM 4 RTN

BLDG ALARM 5 RTN

BLDG ALARM 2 RTN

BLDG ALARM 3 RTN

BLDG ALARM 6 RTN

REMOTE EPO

REMOTE EPO RTN

ON BYPASS RTN

BATTERY CONT RTN

ON INV RTN

ALARM RTN

NOTICE RTN

(Optional)

Figure 35. External Connections for Building Alarm Monitoring

Regardless of how you assign the building alarms, they display as Building Alarm 1,

Building Alarm 2, Building Alarm 3, etc., on the LCD screen of the Monitor Panel. You

should use twisted pair wires for each alarm input and common.