Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio

n

164201261 Rev. F 111503

Connecting Equipment to a Serial Port

You can connect a wide variety of terminals, printers, and computers to each port,

and configure the UPS as the Data Communication Equipment (DCE). Set up the

remote equipment using the appropriate parameters for the mode you select. The

following section provides more information about configuration.

The cables you use for connection depend on the equipment you are connecting

to the UPS. Cables should be no longer than 16m (50 ft). The connectors for

Port 1 and Port 2 on the Communications Panel in the UPS are female, so the

cables should be male. Figure 41 shows the pin assignments for Port 1, and

Table 2 describes them. Figure 42 shows the pin assignments for Port 2, and

Table 3 describes them.

3

2

1

5

4

7

6

9

8

+24V

RS232 TXD

RS232 RXD

NOT USED

RETURN

NOT USED

485 +

485 --

RETURN

PORT 1 (DB--9)

Figure 41. Port 1 Pin Assignments

Table 2. Pin Assignments for Port 1 (DB---9)

Pin # Symbol

Description

Comments

1

+24V

+ 24 volts DC

2

TXD

Transmit Data

Input to UPS

3

RXD

Receive Data

Output from UPS

5

RTN

Return

7

485+

RS485 + Data

8

485---

RS485 --- Data

9

RTN

Return