System output – Powerware 5075 kVA User Manual

Page 130

Advertising
background image

122

Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation

164291261 Rev. F 111503

System Output

Rectifier/Charger Capacity

135% + 6 Kw

DC Filtering

Ripple voltage less than 0.5% peak to peak

UPS Output Capacity

100% current at 0.8 power factor

Output Voltage Regulation

1% (10% to 100% load)

Output Voltage Adjustment

480 VAC nominal, adjustable from 452 VAC

to 508 VAC (60 Hz only)

Output Voltage Harmonic Content

2% max THD, 2% max single (for linear load)

Output Voltage Balance

2% for 100% maximum load imbalance

Output Voltage Phase

Displacement

2˚ for 100% maximum load imbalance

Output Transients

5% for 100% load step or removal

Frequency Regulation

0.005 Hz free running

Synchronous to Bypass

Bypass within voltage limits of +5%, ---8% of

output setting; bypass within 0.5 Hz

Frequency Slew Rate

1 Hz per second maximum

Overload Capability

Up to 125% for 15 minutes

Above125% for 30 seconds

1000% for 10 cycles with bypass

Maximum Output Capability

300% peak for 10 cycles without bypass