Powerware 5075 kVA User Manual

Page 43

Advertising
background image

35

Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio

n

164201261 Rev. F 111503

(ON COMMUNICATIONS

PANEL OF THE UPS)

DB---9 CONNECTOR

TB1 TB2

Figure 15. Wiring an SCM to the UPS

4.

Connect the SCM wiring to the terminal block using the terminations shown in

Table F.

5.

Contact your local field service office for verification and testing of the SCM

and its connections prior to making connections to terminal strip shown in

Figure 16.

6.

Repeat steps 1 through 5 for each SCM you are installing.

7.

If you are installing an RMP or RIM in addition to an SCM, proceed to Chapter

4 or 5, respectively; otherwise, secure the UPS cabinet by reversing the steps

contained in procedure “To Prepare the UPS for Wiring to an RMP, RIM, SCM,

or Remote EPO” of Chapter 2.

Table F. Supervisory Contact Module Wire Terminations

From SCM A

To UPS

Remarks

TB1---4

TB3---1

TWISTED WIRES (4)

TB1---5

TB3---2

TWISTED WIRES (4)

1---2 TURNS PER

TB1---6

TB3---3

3 INCHES

TB1---7

TB3---4

From SCM B (if used)

To UPS

Remarks

TB1---4

TB3---5

TWISTED WIRES (4)

TB1---5

TB3---6

TWISTED WIRES (4)

1---2 TURNS PER

TB1---6

TB3---7

3 INCHES

TB1---7

TB3---8