Chapter 3 installing a remote epo control, Installing a remote epo control – Powerware 5075 kVA User Manual

Page 29

Advertising
background image

21

Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio

n

164201261 Rev. F 111503

Installing a Remote EPO Control

The Remote EPO control arrives as shown in Figure 6. See Drawing

164201261---7 in Appendix A for enclosure dimensions, side views, and

knockout patterns.

EMERGENCY OFF

UNINTERRUPTIBLE POWER SYSTEM

to UPS

to other equipment

Figure 6. Remote EPO Control

To install a Remote EPO control:

1.

Securely mount the Remote EPO station. Recommended locations include

operator’s consoles or exit doors.

2.

Install wiring from the Remote EPO station using ½-in. conduit through the

7/8

-in. knockout in either the top or bottom of the UPS.

3.

Connect the Remote EPO wiring as shown in Tables A and B:

Table A. Remote EPO Wire Terminations

From REPO Station(s)

To Communications

Panel in UPS

Remarks

TB1---4

TB2---1

Twisted wires (2)

TB1---5

TB2---2

Twisted wires (2)

14---18 gauge