Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio

n

164201261 Rev. F 111503

12.

System is now on line (Inverter input supported by battery) and will continue

until the battery is depleted or commercial input power returns.

The following messages appear on the screen:

Status:

System Normal, On Battery

Alarm:

On Battery more than 30 Seconds

Notice:

Bypass AC Under Voltage

Bypass is Not Available

Input AC Under Voltage

13.

Place Power Switch S1 (located in the environmental cabinet) to the OFF

position.

14.

To return the UPS to NORMAL MODE of operation when commercial power

returns, close the feeder breaker.
The UPS can be transferred to bypass and shut down normally.

To Shut Down the UPS from Cold Start:

1.

Place Power Switch S1 (located in the environmental cabinet) to the ON

position.

2.

Place the

BATTERY switch in the OFF position.

3.

Place the

MODE switch in the BYPASS position.

4.

Place Power Switch S1 (located in the environmental cabinet) to the OFF

position.

5.

Open battery breaker

CB2.

6.

Open input breaker

CB1.

To Reset the DC to DC Converter:

1.

Turn

BATTERY switch to OFF.

2.

Wait at least four seconds. Turn

BATTERY switch to NORMAL. The converter

restarts.