Using the menu options – Powerware 5075 kVA User Manual

Page 63

Advertising
background image

55

Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio

n

164201261 Rev. F 111503

Using the Menu Options

The UPS

menus allow you to display data in the information area to help you

monitor and control UPS operation. The following menus and options are

available:

Meters

Displays UPS performance meters for the system or critical load.

Events

Displays the list of Active System Events and a historical log of

system events.

Statistics

Displays statistical information about UPS operations for the

battery, load, or line.

Graphics

Displays a real-time graphic representation of the flow of current

through the internal UPS components.

Setup

Allows you to configure the UPS communications port and set

the date and time for the timestamp.

Figure 25 shows the LCD screen as it appears when you first start the UPS. The Meters

menu is displayed in the menu box, with the System option highlighted. In the

information area, the system meters show their current readings.

Uninterruptible Power System

System Normal
Alarm:

None

Notice: None

Meters

System

Load Amps

Events Statistics Graphics Setup

Input

Output

Bypass

Battery

VAB

480

VBC

VCA

KW

69

KVA

73

IA

IB

IC

FREQ

60.0

PF

0.95

V

540

I

000

Meters

88

480

480

88

88

VAB

480

VBC

VCA

480

480

IA

IB

IC

90

90

90

IN

000

VAB

480

VBC

VCA

480

480

FREQ

60.0

KVA

75

KW

60

PF

0.80

Battery

04 MAY 1998

14:25:45

100%

Percent

Figure 25. System Meters Screen (Typical for Powerware BPIII HE 75 480/480V Unit)

The Input area shows the phase-to-phase voltage, frequency, and phase current of the

incoming utility, followed by the KVA, KW, and power factor measurements. The output

area shows the same information for the power being output by the UPS.
The Bypass area shows the phase-to-phase voltage of the bypass source. The Battery

area displays the DC voltage (V) and the DC current (I) at the inverter side of the DC

to DC voltage converter.