NOTE:

Callout letter

and

map to drawing #164201261---3

,

, ,

DESCRIPTION:

DATE:

DRAWING NO:

3 of 11

INSTALLATION NOTES

SHEET:

REVISION: F

115103

164201261---1

A---4

Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation

164291261 Rev. F 111503

Table C.

INPUT/OUTPUT

Ratings & External Wiring Requirements for

Powerware BPIII HE 50 and 62.5 kVA (400 Volt)

Ratings

Units

Rating

50 Hz

Basic unit rating at

0.8 lagging PF load

KVA

KW

50

40

62.5

50

gg g

INPUT/OUTPUT

VOLTAGE

400

400

A

AC Input to UPS Rectifier

Full Load + Batt. Chg.

(.95min.PF)

3  , (1) gnd

Amps (max)

120

140

A

C

I

N

Minimum conductor size

(number per  )

AWG or

kcmil(ea)

2/0

(1)

3/0

(1)

N

P

U

T

AC Input to Bypass

Full Load Current

3  , (1) gnd

Amps (Nom)

72

90

Minimum conductor size

(number per  )

AWG or

kcmil(ea)

3

(1)

1

(1)

D

C

I

N

P

DC Input from Battery to UPS

(1) positive, (1) negative

VDC

Float VDC

Amps

(2.0V/cell)

120

135

360

120

135

455

P

U

T

Minimum conductor size

(number per pole)

AWG or

kcmil(ea)

3/0

(3)

250

(3)

A

C

O

AC Output to Critical Load

Full Load Current3

3  , (1) Neutral, (1) gnd

Amps (Nom)

72

90

O

U

T

P

U

T

Minimum conductor size

(number per  )

AWG or

kcmil(ea)

3

(1)

1

(1)