Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio

n

164201261 Rev. F 111503

28.

Use Class 1 wiring methods (as defined by the NEC) for control wiring. Install the control

wiring in separate ferrous conduit from the power wiring. The wire should be rated at 24

volts, 1 amp minimum. Control wiring and conduit to be supplied by designated personnel.

29.

Refer to Tables L, M, and N, and to applicable chapters for information about installing

control wiring for options and accessories.

Table L. Control Wiring Terminations

g

Terminal

Description

Terminal Function

TB1

Terminal Block

Not available to customer

TB1

Terminal Block

Not available to customer

TB1

Terminal Block

Remote EPO

TB2
TB2

“On Inverter” Monitoring

TB2

“On Bypass” Monitoring
Summary Alarm & Notice Contacts

Table M. Summary Alarm Relay Contacts

CONTACT RATING:

Maximum Switched Voltage

32 VAC

42 VDC

Maximum Carrying Current

1A

14

15

13

11

12

10

RELAY 1

TB2

RELAY 2