Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation

164291261 Rev. F 111503

The RMP contains a local horn and the following backlit status indicators:

SYSTEM NORMAL

The UPS is energized (either with utility

power or battery backup) and is supplying

conditioned power to the critical load.

NO REDUNDANCY

This indicator applies only to parallel

systems when one cabinet is not

functioning. This feature is not available on

this system.

ON GENERATOR

This alarm means that the UPS input and

bypass are being supplied by the power

from the generator, instead of from the

utility power.

ON BYPASS

The bypass source is supplying the critical

load. Usually this means that the UPS is

not energized. The load is not protected in

Bypass mode, and a horn sounds after 30

seconds.

UPS ALARM

The UPS system is issuing an alarm.

Conditions that affect the current UPS

mode are indicated by the alarm lamps and

horn on the UPS.

ON BATTERY

The UPS battery backup is supplying the

critical load. The utility power is either

interrupted or out of specification. The

SYSTEM NORMAL indicator is also lit.

BYPASS UNAVAILABLE

The UPS system is in Normal mode, but

a bypass source is not within specification.

A horn sounds after 30 seconds.

SHUTDOWN IMMINENT

The UPS is preparing to shut down because the UPS is in Battery mode and the DC

voltage is approaching its low limit.

This light is accompanied by an audible alarm horn.