Normal Mode

In Normal mode, utility AC power is supplied to the rectifier. The rectifier supplies

DC power to the inverter, which then supplies the critical load with AC power. The

rectifier also provides charging power to the battery through a DC to DC voltage

converter. The battery charge condition is monitored by the UPS and reported by a

status indicator on the Monitor Panel. The message “System Normal” appears in

the status area of the LCD screen.

Figure 18 shows the path of electrical power through the UPS system when the UPS

is operating in Normal mode.

Bypass

Rectifier

K4

Input

Input

K3

CB1

(closed)

BATTERY

Path of electrical power

RECTIFIER

INVERTER

Output

TRANSFORMER

BYPASS

DC/DC

CONVERTER

CB2

(closed)

(MBP)

(open)

Input

Isolation

Transformer

(BIB)

(closed)

(MIS)

(closed)

OUTPUT

Figure 18. Path of Current Through the UPS in Normal Mode

If the utility AC power is interrupted or is out of specification, the UPS automatically

switches to Battery mode to support the critical load with no interruption. When

utility power returns, the UPS returns to Normal mode.
If the UPS system becomes overloaded, the UPS switches to Bypass mode. The

UPS automatically returns to Normal mode when the error condition is cleared and

system operation is restored within specified limits.
If the UPS suffers an internal failure, it switches automatically to Bypass mode and

remains in that mode until the failure is corrected and the UPS is back in service.