A---19

Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio

n

164201261 Rev. F 111503

DESCRIPTION:

DATE:

DRAWING NO:

2 of 2

SHEET:

REVISION: A

LOCATION OF UPS POWER TERMINALS

053099

TB1

TB2

Ground

DC Input to UPS

(E4, E5)

(+, ---)

Connect cables

205 and 206

AC Input to

Bypass Transformer

(E13, E14, E15)

(A, B, C Left to Right)

Connect cables 227,

228, and 229

Port 1 (DB---9)

RS---232/485

(J3)

Communication

Panel

Port 2 (DB---25)

RS---232

(J4)

(Optional)

Main Bonding

Jumper

INTERCABINET WIRING

AC Input to

UPS Rectifier

(E1, E2, E3)

(A, B, C Top to Bottom)

Connect cables 250,

251, and 252

Output

Neutral

Connection

(E12)

Connect cable 600 (2)

AC Output

(E9, E10, E11)

(A, B, C,

Top to Bottom

Connect cables

237, 238, and 239

164201261---4

NOTE:

Connections shown are between the

UPS cabinet and Environmental cabinet.

External connections are shown on

sheet 1.