25.

Table I lists the maximum rating for DC input circuit protection devices (circuit breakers).

Table I. Maximum DC Input Circuit Breaker Ratings

Balanced Power System

All Voltage Ratings

Balanced Power 75

700

Balanced Power 62.5

600

Balanced Power 50

450

26.

Your UPS equipment’s operating environment must meet the size and weight requirements

shown in Table J, according to your UPS system configuration:

Table J. Equipment Weight and Point Loading

Weight

Point Loading

Component

Kg (lb)

Kg (lb)

UPS and Environmental Cabinets

1878 (4140)

8 at 235 (518)

27.

The basic environmental requirements for operation of the UPS system are:

Ambient Temperature Range: 0---50˚ C (32---122˚ F)

Recommended Operating Range: 20---25˚ C (68---77˚ F)

Maximum Relative Humidity: 95%