Ups setup configuration – Powerware 5075 kVA User Manual

Page 120

Advertising
background image

112

Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation

164291261 Rev. F 111503

UPS Setup Configuration

Connect the modem to the UPS by connecting one end of the serial cable to the

optional UPS Port 2 DB---25F connector and the other to the modem (refer to

Chapter 13, “Serial Communications”). If using a standard serial cable, a null

modem adapter is required for the connection to the modem.
The Powerware BP III HE UPS can only use optional serial Port 2, DB---25F, for the

Remote Notification option. This connection is located in the serial

communications panel at the base of the UPS cabinet, behind the front door.
The modem operates at only one baud rate because there is no handshaking

between the modem and the UPS. Select the lowest common baud rate (less than

or equal to 2400 baud) compatible with the capability of the UPS interface

equipment. For example, if the computer only has a 2400 baud modem, then the

UPS should be set for 2400 baud. Remember, the remote computer modem can

always slow down to the UPS baud rate, e.g., a 14400 baud modem can run at

2400 baud, but a 2400 baud modem cannot run at 14400 baud.
Following the instructions in Chapter 9, “Using the Monitor Panel” and Chapter 13,

“Serial Communications”, use the LCD screen and pushbuttons on the Monitor

Panel to access the setup screen and configure Port 2 as follows.

NOTE: The modem should be connected to the UPS as described in the modem

manufacturer’s manual before configuring the UPS communications port.

<MODE>

Remote Notify

<RATE>

The baud rate at which the modem will communicate

to other modems, 2400 baud maximum.

<DATA/STOP>

8 1 Standard 8 data bits, 1 stop bit, no parity.

<HANDSHAKING>

Disabled

<SAVE>

Yes. To save new configuration.

The handshaking feature listed is for UPS-to-terminal handshaking, not

UPS-to-modem handshaking. Setting the handshaking to “modem” has no effect.

If the remote terminal has buffering problems because of excessive data transfer

rate from the UPS, XON/XOFF handshaking can be selected to resolve this issue.

The user must make sure that the modem (not the remote terminal) at the remote

terminal end of the connection is configured for either hardware handshaking or

none at all. This is required so that the modem does not attempt to trap the

XON/XOFF characters and prevent them from being transmitted to the UPS.

Advertising