Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
30.
The Remote EPO feature opens all breakers and contactors in the UPS cabinet and
isolates power from your critical load. Local electrical codes may also require tripping
upstream protective devices to the UPS.
Table N. Remote EPO
Remote EPO switch rating is 24 VDC.
1 Amp minimum if supplied by user.
NOTE: This switch must be a dedicated switch
not tied into any other circuits.
1
2
REMOTE
EPO
SWITCH
TWISTED
WIRES (2)
TB2