2 modular cabinet powering restrictions, Technical product manual - dct1900 – Nortel Networks DCT1900 User Manual

Page 113

Advertising
background image

Technical Product Manual - DCT1900

Configuration Directions, Limitations of the System

Config-DCT1900/R8/mw

2-3

© 2000-2005

2.2

Modular Cabinet Powering Restrictions

Although the Modular Cabinet has space for 9 boards, not all board combinations are allowed due
to power limitations of the DC/DC converter on the backplane. This converter is specified as
follows:
+5 V

can supply 40 W at maximum

+12 V

can supply 12 W at maximum

-12 V

can supply 12 W at maximum

total

must be

<

40 W

Table 2–1 shows the power consumption per board type. From this table, it can be calculated if a
configuration matches the power requirements. The values given to the

±12V of the LTU indicates

the power consumption in the case where all LTU circuits are off hooks.

Note:
Due to a minimum required power consumption from the DC/DC converter, at least two boards
must be present in each cabinet.

Table 2–1 Power Consumption per Board

B o a r d T y p e

5 V

+ 1 2 V

- 1 2 V

C P U - 2 R E X - B R D 9 0 3 3

R E X - B R D 9 0 3 4

6 W

C P U R E X - B R D 0 0 0 4

9 . 6 W

1 W

1 W

S P U - S R E X - B R D 0 0 1 7

3 . 5 5 W

S L U R E X - B R D 0 0 1 5

6 . 9 W

C L U - S R E X - B R D 0 0 1 6

3 . 4 5 W

C L U R E X - B R D 0 0 1 4

3 . 6 W

D T U - E 1 , C C S / C A S

R E X - B R D 0 0 0 2

4 . 5 W

D T U - T 1 , C A S

R E X - B R D 0 0 2 1

6 W

D T U - T 1 C C S
R E X - B R D 0 0 2 1

6 W

L T U R E X - B R D 0 0 0 7

1 . 5 W

. 7 5 W

. 7 5 W

L T U - 2 R E X - B R D 0 0 1 9

2 . 5 W

D L U R E X - B R D 0 0 2 3

A W S 1 0 2 4

A W S 1 0 2 5

A W S 1 0 2 6

6 . 5 W

1 . 2 W