Technical Product Manual - DCT1900

Installation Instructions, Modular Cabinet – Power Cabling

Install-DCT1900/R8/mw

19-9

© 2000-2005

Factory Fitted Power Cabling
The Modular Cabinet is delivered with the following powering cables fitted:

z

Cable TRENB 101 02 (190248) between the filter and the lower fuse holders (see Figure 19–
11).

z

Cable TRENB 101 04 (#190250) between the switch and the lower two fuse holders.

z

Cable between the switch and the upper fuse holders. The end of the cable with piggy-back
faston is connected to the switch.

z

Cable between the switch and connector PW–BP on the MCCB. Connects to piggy-back
faston on the switch.

z

Cable between the upper fuse holders and connector X112, X113 on the backplane (see
Figure 19–12).

z

Cable #190253 (red cable) in two locations: between terminal block A and filter and between
terminal block B and MCCB terminal PW-EXT (see Figure 19-10).

z

Cable #190254 (black cable) in two locations: between terminal block A and filter and
between terminal block B and MCCB terminal PW-BP (see Fig. 19-10).

All cables are connected with the red wires (+) connected at the left–hand side except for PW-EXT
connection. The red wire of cable is connected to connector X112(+).

In the following paragraphs it is assumed that the cables are fitted as described above. If you
altered the wiring, change it as described above.

Fig. 19-10 Power Connection to the Modular Cabinet

Red

Black

Botton view

MCCB

+

|

Red

Black

Additional wires to external
-48V supply

L

+

Red

Black

_

B

A

+

_

-48V supply

Warning

Torque the terminal screws
to 7 in./lb.

PW-EXT

Additional wires to

external -48Vdc

-

+

+

-