Alpha Technologies AMPS80 HP User Manual

Page 100

Advertising
background image

Doc. #: 026-069-B0 Rev F

98

9.1 Specifications for 48/120 Inverter Module

General specifications:

EMC (immunity)

EN 61000-4

EMC (emission)

EN55022 (Class A), FCC 47 VFR Part 15, class A

Safety

IEC 60950, UL 1778 Issue 4

Cooling

Forced Air

MTBF

240000 hrs

Efficiency (typical)

Enhanced Power Conversion

94%

On Line

89%

AC Output Power

Nominal

2500 VA

Resistive Load

2000 W

Overload Capacity (short)

150% @ 5 s

Overload Capacity (permanent)

110%

Nominal

48 V

Range (V dc)

40 to 60 V

Nominal Current (@40 Vdc)

56 A

Max input current (5 s)

84 A

Voltage Ripple

2 mV

AC Input Specifications

Nominal voltage (AC)

120 Vac

Voltage range (AC)

90 to 140 Vac (adjustable)

Power factor

> 99%

Frequency range (selectable)

60 Hz

Frequency Tolerance

± 3 Hz (Adjustable)

AC Output

Nominal (AC)*

120 Vac Accuracy 2%

Frequency

60 Hz (Same as input frequency in EPC mode)

Frequency accuracy

0.03%

Transient load recovery time

0.4 ms

Transfer Performance

Maximum Voltage interruption

0 s

Total Transient voltage duration

0 s

Environmental

Operating Temperature:

-20 to +40°C

Storage Temperature:

-40 to +70°C

Humidity:

Up to 95% non-condensing

Elevation:

<1500M

Miscellaneous

Dimensions:

2 RU H x 102 mm W x 435 mm D

Weight:

5 kg (11 lb.)

Advertising