10.4 Inverter Parameters (ID 51 – 550)

;60;

;Input Source (AC : 0, DC : 100);

;0; ;%;

x

Record of priority source

x

0 –> Priority feed from ACin (converter AC/AC - AC/AC mode), Default setting

x

100 –> Priority feed from DC (converter DC/AC - On Line mode)

;61;

;AC

in

Mode (0 : normal, 1 : Safe);

;0; ; ;

x

Opens the AC

in

inlet relay

x

0 –> Normal running in AC/AC mode, Default setting

x

1 –> ACin inlet relay is open and so the system is insulated from the Mains

;62;

;Walk-in Mode (0 : No, 1 : Yes) ;

;1; ; ;

x

Walk-in mode allows a progressive comeback, slowly removing DC power while slowly

increasing AC power

x

0 –> no progressive switching

x

1 –> progressive switching at 10% per second

;70;

;Number of phases ;

;3; ; ;

x

Record of number of phases : 1 (Single phase), 2 (2 phase), 3 (3 phase)

x

Range: 0 - 8, Default: 1

;71;

;Mode (0 star; 1 Delta) ;

;1; ; ;

x

Record of the protection for working on Delta load

x

The mode, star or delta, allows configuration of automatic protection when the load is a

delta connection (an engine for instance). This protects the load when 1 phase is lost. The

protection consists of switching off all inverters.

x

0 –> no delta load protection, Default setting

x

1 –> Delta load protection available

;75;

;Free running Frequency ;

;50.0; ;Hz;

x

Record of the Inverters system frequency, 50 or 60 (default)