6. System Operation
6.1 Inverter Module Indicators
Output power
indicator LEDs
Status LEDs
Figure 35 —
Fig. 4.1 Inverter module status, power LEDs
6.1.1 Status LEDs
Inverter Status LED
Description
Remedial action
OFF
No input power or forced stop
Check AC input
Permanent green
AC Intput OK, normal operation
None required
Flashing green
Inverter OK but conditions are not
within normal parameters
Check upstream and surrounding equipment
Flashing green/orange alternating Recovery mode after boost
(10 In short circuit condition)
Wait for a while
Permanent orange
Starting-up mode
Wait
Flashing orange
Modules cannot start
Insert CXC
Flashing red
Recoverable fault
Wait or attempt to clear fault condition by
removing and reinserting the module
Permanent red
Non recoverable fault
• Attempt to clear fault condition by
removing and reinserting the module
• Download CXC inverter alarm logs
• Record the alarm(s)
• Send module back for repair
AC input
AC output
DC input