4.2 Recommended Installation Layout

In the unlikely event that internal components need repair, 1 m access around the unit is

recommended.

NOTE:

Minimum required clearances around the cabinet:

• Rear: 18" (46 cm)
• Sides: no clearance required.

However for 75 kVA hybrid systems and systems with TVSS option, 36" (100 cm) clearance to the left

side of the cabinet is strongly recommended for ease of service

• Top: 12" (30 cm)
• Front: 36" (100 cm)

OTHER EQUIPMENT

OR WALL

OTHER EQUIPMENT OR WALL

3 Feet

The 1m recommended

clearance only applies to 75kVA

hybrid systems with TVSS

option (for ease of service).

Minimum distance

for ventilation

Minimum distance

for service

Minimum distance

for ventilation

Rear

Front

OTHER EQUIPMENT

OR WALL

18in

6.0in

[46cm]

[15cm]

[1 m]

3 Feet

[1 m]

Figure 10 —

Installation layout and clearances