Alpha Technologies AMPS80 HP User Manual

Page 106

Advertising
background image

Doc. #: 026-069-B0 Rev F

104

;80;

;Short Circuit Voltage Threshold;

;80; ;V;

x

Minimum Voltage Threshold where module considers that outlet is in short circuit

x

Adjustable from 20 to 100 Vac, default: 80 Vac

;81;

;Short Circuit Hold Time;

;60.0; ; sec;

x

Time Duration when the module tries to eliminate the short-circuit existing on the outlet

x

When this time expires and the voltage is less than the value on line 80, the module stops.

x

Adjustable from 0.1 to 600 sec, default: 60 sec

;82;

;Booster 10 x I

in

(0 : OFF, 1 : ON) ;

;1; ; ;

x

Turns off the Booster option which generates a current of 10 x I

in

for 20ms in case of short-

circuit.

;90;

;Max current (as percentage of nominal current);

;110; ;%;

x

Maximum Current that module can supply.

x

Adjustable from 100 to 110 % for AIM2500

;91;

;Max power (as percentage of of nominal power) ;

;110; ;%;

x

Maximum Power that the module can supply.

x

ALWAYS RECORD THE SAME VALUES for 90 and 91

;92;

;Max Overload Duration);

;15; ;sec;

x

Maximum Time Duration when module can run with overload.

x

Adjustable from 0 to 15 sec, default: 15 sec

;100;

;Synchronization Tracking Speed;

;0; ; ;

x

Speed with which the module tries to synchronize AC

out

x

Possible values:

Speed

Value

Frequency (Hz/sec)

very fast

-2

2.5

fast

-1

1.25

normal (default)

0

0.5

slow

1

0.25

very slow

2

0.1