3 dc connections, 1 dc battery cabling – Alpha Technologies AMPS80 HP User Manual

Page 45

Advertising
background image

43

Doc. #: 026-069-B0 Rev F

5.3 DC Connections

• Access to connection points is provided from the front of the system rack.

• DC wires enter the cabinet either through the top or the bottom of the cabinet.

• A low voltage disconnect should be provided with the battery system.

Figure 22 —

DC connections - top view

DC+ bus

: DC1, DC2, DC3, DC4 input con-

nectors shown with one 4DC tie bar

DC- bus

: DC1,

DC2, DC3, DC4

5.3.1 DC Battery Cabling

DC battery cable terminations are de-

signed for two-hole spade lugs crimped to

the cabling, then attached to the bus bars.

Depending upon the gauge of the input

wiring used, the connections may be made

either singly or with two back-to-back lugs

per mounting hole.

Each bar (DC+, DC-) can accept seven

2-hole ½" mounting lugs on 1-3/4" centers

or seven 2-hole 3/8" lugs on 1" centers.

Torque specifications for DC wiring (3/8"

bolts that attach the DC lugs at the back

of the DC distribution box) are 190 – 240

inch/lbs (21.5 – 27.1 N-m).

Input cabling

3/8" or 1/2" hardware

Tie bar

Bus bar

Figure 23 —

Cabling and hardware arrangement