7.9 Synchronization After Maintenance or Repair

Implement the following sequence before switching the unit from bypass mode to inverter mode.

1. Switch on the inverter input breaker. Wait for the inverters to synchronize to the line, and for all status

LEDs to turn green.

2. Switch on the inverter output breaker.

3. If present, switch the internal bypass switch to AMPS80 HP system. If present, switch the external bypass

switch to AMPS80 HP system.