Alpha Technologies AMPS80 HP User Manual

Page 40

Advertising
background image

Doc. #: 026-069-B0 Rev F

38

Figure 17 —

Representative system wiring for AMPS inverter or hybrid system with MBS with single AC input feed.

4.6.2 AMPS80 HP with External Maintenance Bypass Switch

These diagrams show the logical internal connections. They are not a detailed representation of the actual

internal system wiring.

Figure 18 —

Representative system wiring for AMPS inverter system with independent AC input feed for MBS

Generator

MAIN

Distribution

Panel

Utility

Dedicated

UPS

Distribution

Panel

Critical

Systems

Power

External

Maintenance

Bypass

Switch

UPS

BYPASS

Automatic

Transfer

Switch Break

Before Make

Rectifier

(optional)

Inverters

Make before break

manual bypass

switch (optional)

AMPS 80 HP

AC Input

AC Output

Battery

Connection

DC breakers

(optional)

AMPS80 HP Installation Diagram for

single AC input feed for the

Inverter/MBS and Rectifiers

Generator

MAIN

Distribution

Panel

Utility

Dedicated

UPS

Distribution

Panel

Critical

Systems

Power

External

Maintenance

Bypass

Switch

UPS

BYPASS

Automatic

Transfer

Switch

Rectifier

(optional)

Inverters

Make before break

manual bypass

switch (optional)

AMPS 80 HP

Inverter AC Input

AC Output

Battery

Connection

DC breakers

(optional)

400A for AMPS80-3-75

AMPS80-2-40

200A for AMPS80-3-30

AMPS80-2-20

AMPS80 HP Installation Diagram for

separate AC input feeds for the

Inverter/MBS and Rectifiers

Rectifier AC Input

Advertising