Alpha Technologies AMPS80 HP User Manual

Page 101

Advertising
background image

99

Doc. #: 026-069-B0 Rev F

9.2 Specifications for 48-1.8 kW Rectifier

Rectifier Module Input Voltage, Output Current, Power

AC Input Voltage

Rectifier shelves

Max # of Rectifier 

Modules

Max DC output VA

Current (Adc)

120

2

8

192 Adc

120/240 Vac

2

8

300 Adc

Power Module Output

Voltage

42 to 60 Vdc within rated limits

Current

37.5 A maximum @ 48 Vdc (nominal input)

~24 A @ 48 Vdc (115 Vac input)

Power

1800 W maximum @ nominal input

~1150 W @ 115 Vac input (de-rated linearly to 900 W @ 90 Vac)

Static Load Regulation

Better than ±0.5% for any load change within rated limits

Dynamic Load Regulation

Better than ±2% for 40% – 90% – 40% (50% load step)
[output shall recover to static limits within 10 ms]

Static Line Regulation

Better than ±0.1% for any change in input voltage within rated limits

Dynamic Line Regulation

Better than ±1% for any change in input voltage within rated limits (output

voltage shall recover to static limits within 2 ms)

Hold-up Time:

>10 ms

Time Stability:

=0.2% per year

Temperature Stability:

<170 ppm/°C over the operating range

Heat Dissipation:

<607 BTU per hour (per rectifier module)

Electrical Noise:

<32 dBrnC (voice band)

<30 mVrms 10 kHz to 10 MHz (wideband)

<150 mVp-p 10 kHz to 100 MHz

<1 mV (psophometric)

Acoustic Noise:

<60 dBa @ 1 m (3 ft.) @ 30°C (86°F)

EMI:

FCC Part 15, Class B:

Advertising