Table k — alarm codes – Alpha Technologies AMPS80 HP User Manual

Page 94

Advertising
background image

Doc. #: 026-069-B0 Rev F

92

Table K — Alarm Codes

Alarm Type

Description

Cause

Solution

44

BACKFEED

ERROR

ACin is supplied by the

ACout of the module

Grid is not present and there

is a short circuit between

ACin and ACout

45

Vint TOO HIGH

Same as error 10 but recoverable

65

TSI COM BUS

FAIL

The inverter doesn't see

itself on the bus TSI

Communication problem

Hardware problem. Replace

inverter

66

T2S COM BUS

FAIL

The inverter doesn't see

itself on the bus T2S

Communication problem

Hardware problem. Replace

inverter

67

TSI COM BUS

FAIL

No synch top received on

TSI BUS

No Sync top from TSI inverter Hardware problem. Replace

inverter

68

T2S COM BUS

FAIL

No sync top received on

T2S BUS

No sync top from T2S

inverter

Hardware problem. Replace

inverter.

69

LOADSHARING

LOW

The inverter gives less

power than other inverters

in parallel

This alarm should disappear by

itself. If it remains permanent,

the module probably has a

problem.

70

LOADSHARING

HIGH

The inverter gives more

power than other inverter in

parallel

This alarm should disappear by

itself. If it remains permanent,

the module probably has a

problem.

71

VOUT

CHANGING

Output voltage is changing

its nominal value

Happens when there is a

config change to the voltage- 

lasts 1 min for a change from

100V to 120V

NEVER INSERT A NEW

MODULE WHILE THIS IS IN

PROGRESS!

N/A

72

OVERLOAD

CURRENT

The load current is greater

than the current available

from inverter

Load too high or some

inverters are failing.

Reduce load or add inverter to

the system.

73

COM BUS

MISMATCH

The modules seen on bus

A are different that modules

see on bus B

Alarm- triggered when it sees

more or less modules on bus

A vs bus B - used to identify

a module problem while the

module is still running

Hardware problem. Replace

inverter

74

IMMINENT

START

Reported from a stopped

module 10 seconds before it

is going to start

Start up procedure

N/A

75

BOOSTER NOT

READY

The boost function is not

allowed at this time

Less than 60 second, after

previous boost action

Wait 1 minute to recover from

the situation

76

OVERLOAD

NOT READY

The overload function is not

allowed at this time

Less than 55 second, after

previous overload status

Wait 1 minute to recover from

the situation

77

TEMP

DERATING

Temperature measured

from the heat sink - 88°C for

AIM2500 module and 70°C

for AIM1500 module

Heat sink temperature over

rating

Check temperature inside

inverter. Check room

temperature. Replace FAN.

Replace inverter

78

OVERLOAD

POWER

The load power is greater

than the power available

from inverter

Requested power greater

than available power

Reduce load or add inverter on

the system.

79

EEPROM

DEFECT

The EEPROM has a

problem

Replace Inverter

Advertising