Maintenance, 1 preventive maintenance, 2 recommended maintenance schedule – Alpha Technologies AMPS80 HP User Manual

Page 79: 3 tools, spare parts and equipment, Table i — tools

Advertising
background image

77

Doc. #: 026-069-B0 Rev F

WARNING!

WARNING: HIGH VOLTAGE AND SHOCK HAZARD Use extreme care when working in-

side the enclosure/shelf while the system is energized. Do not make contact with live com-

ponents or parts. Static electricity may damage circuit boards, including RAM chips. Always

wear a grounded wrist strap when handling or installing circuit boards. Ensure redundant

modules or batteries are used to eliminate the threat of service interruptions while perform-

ing maintenance on the system’s alarms and control settings.

7. Maintenance

7.1 Preventive Maintenance

This equipment requires regular maintenance. The maintenance must be done by qualified service personnel

only. Contact Alpha Technologies at 1-888-462-7487 for any assistance with maintenance.

7.2 Recommended maintenance schedule

Task:

Interval

Clean ventilation openings

1-6 month

Inspect all cable connections, re-torque if necessary

1 year

Verify alarm/control settings

1 year

Verify alarm relay operation

1 year

Verify circuit breaker operation

1 year

7.3 Tools, Spare Parts and Equipment

Table I — Tools

Required

Service /Maintenance

Commissioning

Torque wrench

X

X

#2 Philips screw driver

X

X

#2 flat head screw driver (3/16") width head

X

#1 flat head screw driver (1/8") width head

X

Small flat head screw driver (1/16") width head

X

X

9/16" hex driver

X

3/8" hex driver

X

7/16" combo wrench

X

7/16" flat gear ratchet

X

9/16" combo wrench

X

9/16" flat gear ratchet

X

11/16" combo wrench

X

11/16" flat gear ratchet

X

6" ratchet extension

X

3" ratchet extension

X

Advertising