15 alarms – Alpha Technologies AMPS80 HP User Manual
Page 71

69
Doc. #: 026-069-B0 Rev F
6.3.15 Alarms
Standard Inverter Alarms
Alarms for the following conditions can be configured from the
Alarms > Configure Alarms
menu category
(refer to the controller software manual for more details on alarm configuration):
Alarm Name
Alarm Condition
Inverter Major Fail Count
Number of failed Inverters equals or exceeds a user configured threshold
Inverter Minor Fail Count
Number of failed Inverters equals or exceeds a user configurable
threshold
Inverter Comms Lost
Controller loses communications with any one inverter. The number of
inverters must be correctly identified in the Inverters > Set Output menu.
Inverter AC Input Fail
Main AC input of the inverter is lost
Inverter Alarm
Any individual or system alarm is detected
Figure 51 —
Configure alarms window
Custom Inverter Alarms—Mapping Alarms to Relays
Custom inverter alarms can be mapped through the digital inputs to available relays. Refer to the latest ver-
sion of the CXCU Controller software manual.