3.3 120V/240V Split Phase or 120/208V 2-Pole Systems

The recommendations in Table D are for reference only. A registered professional engineer

must review and approve or modify these recommendations in compliance with applicable

national and local electrical and building codes.

NOTE:

Table D — 40 kVA, split-phase, 2-pole systems (AMPS80-2-40 series), single AC feed

Model

AMPS80-2-40

AMPS80-2-

40-H2

AMPS80-2-40,

MBS

AMPS80-2-

40-H2, MBS

AC

input

Feed

Single

Single

Single

Single

AC input voltage

120/208 V

or 120/240 V

120/208 V

or 120/240 V

120/208 V

or 120/240 V

120/208 V

or 120/240 V

Full load AC input current per phase

148 A

225 A

179 A

256 A

AC input poles & wiring

3 w + G

3 w + G

3 w + G

3 w + G

Wiring

2-pole

2-pole

2-pole

2-pole

Recommended

AC input breaker/fuse2

200 A

300 A

225 A

350 A

Recommended

AC input wire size

90ºC copper1

NEC 30ºC

#2/0

250 kcmil

#3/0

350 kcmil

CEC 30ºC

#3/0

300 kcmil

#4/0

See dual feed

NEC 40ºC

#3/0

250 kcmil

#3/0

See dual feed

CEC 40ºC

#3/0l

300 kcmil

#4/0

See dual feed

AC

output

Total maximum AC output

40 kVA, 32 kW

40 kVA, 32 kW

40 kVA, 32 kW

40 kVA, 32 kW

AC output voltage

120/208 V

or 120/240 V

120/208 V

or 120/240 V

120/208 V

or 120/240 V

120/208 V

or 120/240 V

AC output poles & wiring

3 w + G

3 w + G

3 w + G

3 w + G

Wiring

2-pole

2-pole

2-pole

2-pole

AC output current per phase

167 A

167 A

167 A

167 A

Installed inverter input

& output circuit breaker

250 A

250 A

250 A

250 A

Recommended

AC output wire size

90ºC copper1

NEC 30ºC

#4/0

#4/0

#4/0

#4/0

CEC 30ºC

250 kcmil

250 kcmil

250 kcmil

250 kcmil

NEC 40ºC

250 kcmil

250 kcmil

250 kcmil

250 kcmil

CEC 40ºC

300 kcmil

300 kcmil

300 kcmil

300 kcmil

AC input & output

connection

terminals

Box lugs are rated for either Aluminum or Copper wire, 350 kcmil to #6 AWG. Fasten clamping screw to

42 N-m (375 in-lbs) for #1 AWG to 350 kcmil wire or 23 N-m (200 in-lbs) for #6 to #2 AWG wire.

Note 1

Inverter AC Input & AC Output connections: Calculations based on full load and charging current, 0.8 derating with 5

current carrying conductors, (L1,L2,L3,2XN) due to possible high harmonic content load. Temperature correction factor

applied when needed.

Note 2

Maximum AC utility service protection feeding the AMPS80 HP is 400 A. The actual supply circuit breaker must be sized appropriately

for the supply wire used. Consult your local and national electrical codes. The AC source must be limited to 18 kA short circuit current.

Double neutral is strongly recommended for AC output wiring (and AC input wiring to the MBS) for 3Ф systems with significant non-

linear (ie rectified capacitive) loads. Because the AC input to the inverters is power factor corrected, AC wiring solely to the inverters 

does not require double neutral wiring.